Magtech General Construction & Trading Pte Ltd replaced a corroded ball float valve on the domestic water tank at 9 Joo Koon Crescent, Singapore.

Ball float valve replacement at 9 Joo Koon Crescent Singapore - compartment floor washed with new valve
Compartment floor washed with new valve

PROJECT INFORMATION

PROJECT OVERVIEW

The existing valve had corroded to the point where it could no longer shut off. Instead of closing when the tank was full, it kept releasing water continuously, so the tank was constantly overflowing. It is one of the most common faults on any water tank, and one of the easiest to overlook.

A ball float valve controls how a tank fills. As the water rises, the float rises with it and closes the valve when the tank reaches its top water level. Once the valve body and seat corrode, it can no longer seal, and water keeps passing through it. Nothing appears wrong from the outside – the tank stays full and the overflow quietly carries the excess away – but water is running to waste around the clock.

We replaced the old valve with a new 80mm (3-inch) Norika ball float valve with a stainless steel float. While the affected compartment was drained for the work, it was also washed down, and a water sample test was carried out before it went back into domestic service.

The tank has two compartments, and only the affected one was taken out of service. The other compartment stayed in use throughout, so the building kept its domestic water supply while the work was carried out.

 

Our Approach

  1. Tracing the Overflow to the Valve

A tank that overflows constantly almost always points to the inlet. On inspection the ball float valve was heavily corroded and visibly passing water even with the compartment full.

  1. One Compartment Down, One in Service

Only the affected compartment was isolated and drained. The second compartment carried on supplying the building, which is exactly what a two-compartment tank is designed to allow.

  1. Replacing the Valve

The corroded valve was removed through the manhole and a new 80mm (3-inch) Norika ball float valve fitted in its place.

  1. Washing and Water Testing

With the compartment already drained and a corroded fitting just removed from it, the compartment was washed down and a water sample test carried out before it returned to domestic use.

  1. Refilling and Checking Shut-Off

The compartment was refilled and the new valve checked to confirm it closes properly at the top water level, bringing the overflow to a stop.

01
Scope of work
  • Inspection of the overflowing compartment and the existing ball float valve
  • Isolation and draining of the affected compartment, with the other compartment kept in service
  • Removal of the corroded ball float valve
  • Supply and installation of a new 80mm (3-inch) Norika ball float valve
  • Washing of the affected compartment
  • Water sample test
  • Refilling and checking that the new valve shuts off at the top water level
  • General cleaning on completion
02
Project outcome
  • Constant tank overflow stopped
  • Corroded ball float valve replaced with a new 80mm (3-inch) Norika valve
  • Affected compartment washed and water sample tested
  • Second compartment kept in service throughout, with no loss of domestic supply
  • New valve confirmed shutting off correctly at the top water level

Why This Matters

A passing ball float valve is one of the quietest faults a water tank can have. The tank never runs dry, nothing stops working, and the overflow does exactly what it was designed to do – carry the excess away. The first sign is often an unexplained rise in the water bill, or water running from an overflow pipe that nobody had reason to look at.

The fix itself is routine, but how it is carried out matters. On a two-compartment tank there is no need to cut the building’s water supply: one side comes out of service while the other keeps running. And while a compartment is drained and open, it is the right moment to wash it and test the water before it goes back into domestic use, rather than simply swapping the valve and refilling.

With over 35 years of experience and more than 4,000 water tanks installed across Asia, Magtech carries out water tank repairs of every size across Singapore, from a single fitting to a full tank replacement.

35+

Years of experience

in sectional water tanks

4,000+

Tanks installed

across Singapore and Asia

Our team will respond within 24–48 hours.

◉ NEED A FASTER RESPONSE? WhatsApp Our Team →
PROJECT GALLERY

Repair Photos

DISCUSS YOUR PROJECT

Enquire About 9 Joo Koon Crescent Tank Installation, Replacement or repair

Send us the required effective capacity, available space, intended water use and project drawings. Our team can review the information and advise on the next step.

Our team will respond within 24–48 hours.

◉ NEED A FASTER RESPONSE? WhatsApp Our Team →

Other related projects

Project: 81 Ellington Square

Project: Grand Villa, Sihanoukville

Project: 2 Second Chin Bee Road