Pricing update from October 2026: Revised pricing will apply due to continued increases in material, manufacturing and logistics costs.
ST Engineering Data Centre, 3 Ang Mo Kio Electronics Park Road
New Built Project

ST Engineering Data Centre, 3 Ang Mo Kio Electronics Park Road

Magtech General Construction & Trading Pte Ltd supplied and installed a large FRP (GRP) sectional panel water tank on the roof of the ST Engineering data centre at 3 Ang Mo Kio Electronics Park Road, Singapore. The tank holds make-up water for the facility’s cooling system, where a reliable top-up supply matters as much as the chillers it serves.

FRP water tank installation at ST Engineering data centre, Ang Mo Kio, Singapore Feat
Partitioned tank on special I-beam skid base - roof manholes, vents and guardrail

PROJECT INFORMATION

PROJECT OVERVIEW

The tank was not taken from a catalogue. Magtech’s team proposed the tank size from two constraints: the storage capacity the cooling system required, and the plinth that already existed on the roof. The result is a single tank of 10(5+5)m x 3m x 4m (H), divided by a partition into two 5 m compartments so that one half can be isolated for inspection while the other keeps feeding the cooling plant. A special I-beam skid base was designed to carry the tank on the existing plinth, and the beams were upsized for the full 4 m water load.

The tank was built from SS245 grade FRP panels at the 4 m height limit of the standard. A 1 m HDG guardrail runs around the roof perimeter, and two external HDG ladders with safety cages give access to the manholes at each compartment, with a level indicator on each. The layout was revised during design: the original proposal of two tanks of 4(2+2)m x 4m x 4m (H) was consolidated into one partitioned tank on a strengthened base.

01
Scope of work
  • Tank sizing proposal from the required cooling make-up capacity and the existing roof plinth
  • Design of a special I-beam skid base, upsized for the tank load, to suit the existing plinth
  • Supply and installation of one SS245 grade FRP sectional panel water tank, 10(5+5)m x 3m x 4m (H)
  • Partition wall, internal tie-rod reinforcement, manholes, air vents and level indicators
  • 1 m HDG guardrail along the full roof perimeter of the tank
  • Two external HDG ladders with safety cages
  • Flanged nozzles for inlet, outlet, overflow, drain and balancing connections
  • Filling, leak check and general cleaning on completion
02
Project outcome
  • One 10(5+5)m x 3m x 4m (H) FRP make-up water tank installed on the ST Engineering data centre roof
  • Tank sized by Magtech to the required capacity and the existing plinth, with a purpose-designed skid base
  • Two-compartment layout keeps cooling make-up available during maintenance
  • Strengthened I-beam skid base and SS245 grade panels for the 4 m water head
  • Perimeter guardrail and caged ladders fitted for safe roof-level access
  • Tank filled, leak-checked and handed over to the M&E contractor

Our Approach

1. Sizing to the Capacity and the Existing Plinth

A data centre’s make-up tank has to hold the capacity the cooling design calls for, and on this roof it also had to sit on a plinth that was already built. Magtech worked both constraints together and proposed one long partitioned tank, 10 m by 3 m, rather than the two 4 m by 4 m tanks first considered. The single tank gave the same redundancy with one base, fewer connections to the roof pipework and one set of access equipment.

2. A Skid Base Designed for the Site

Where the plinth layout did not match a standard skid, Magtech designed a special I-beam skid base to spread the tank load onto it. At 4 m the loads on the base and the internal tie rods are at the top of the SS245 range, so the beams were upsized and the tank reinforced to suit before the panels were set.

3. Safe Access at Height

A tank of this height needs a guardrail on the roof and caged ladders on the sides. Both were supplied and installed with the tank so the manholes, vents and level indicators can be reached safely for the life of the installation.

 

Why This Matters

A data centre cannot let its cooling towers run short of make-up water, so the storage tank has to be sized generously, split for maintenance and built to stay in service for decades. It also has to fit the roof it is given. FRP sectional tanks do this well: the panels do not corrode, the modular format allows a long footprint like 10 m by 3 m on an existing plinth, and a partition is a simple way to build in redundancy. The limiting factor is height, and a 4 m tank is where the base and reinforcement design has to be done properly.

With over 35 years of experience and more than 4,000 water tanks installed across Asia, Magtech continues to deliver FRP water tank installation for data centres, industrial plants and commercial buildings across Singapore.

35+

Years of experience

in sectional water tanks

4,000+

Tanks installed

across Singapore and Asia

Our team will respond within 24–48 hours.

◉ NEED A FASTER RESPONSE? WhatsApp Our Team →
PROJECT GALLERY

New Built Photos

DISCUSS YOUR PROJECT

Enquire About ST Engineering Data Centre, 3 Ang Mo Kio Electronics Park Road Tank Installation, Replacement or repair

Send us the required effective capacity, available space, intended water use and project drawings. Our team can review the information and advise on the next step.

Our team will respond within 24–48 hours.

◉ NEED A FASTER RESPONSE? WhatsApp Our Team →

Other related projects

Project: 6 Chestnut Close

Project: Koh Norea Tower 1

Project: Jurong Island