HDG Pressed Steel Water Tanks in Singapore

A pressed steel water tank is a bolted sectional tank built from hydraulically pressed mild steel panels, hot-dip galvanised to ISO 1461. In Singapore it is the standard choice for fire protection storage — sprinkler, hosereel and wet riser tanks — because fire specifications are written to SS 22 and to LPCB listing rather than to any single manufacturer.

Installation, replacement and repair support across Singapore and Asia.

Tank material

Hot-Dip Galvanised Mild Steel

HDG Pressed Steel Fire Protection Tanks product image cutout magtech
PRIMARY APPLICATION

Fire protection water storage

01
Fire specification

SS 22

02
Standard modules

1.0 m or 1.22 m

03
Typical service life

20–25 Years

TANK APPLICATIONS

HDG Pressed Steel Tank for Fire Protection and Non-Potable Water Storage

HDG pressed steel tanks provide durable, large-capacity water storage for commercial, industrial and infrastructure fire protection systems.
01

Sprinkler Water Tanks

Dedicated water storage for automatic sprinkler systems designed to control and suppress fires.

Automatic sprinklers
02

Hosereel Water Tanks

Reliable fire-water storage supporting manual hosereel systems within commercial and industrial buildings.

Manual firefighting
03

Wet-Riser Water Tanks

Fire-water storage for wet-riser systems serving multiple levels in high-rise developments.

High-rise buildings
04

Selected Non-Potable Uses

Suitable for selected make-up and building-service water duties where the required finish or lining is confirmed.

Confirm project specification
WATER TANK COMPLIANCE

What Standards Apply to HDG Pressed Steel Tanks?

The tank design, plate thickness, galvanised finish and required fire-protection listing should all be confirmed before comparing quotations.
22
SINGAPORE STANDARD

Singapore fire-protection specifications commonly reference SS 22 pressed steel sectional tanks, together with LPCB listing where required by the project.

SS 22 is a Singapore Standard rather than an SCDF certification. Project fire specifications may reference the standard through applicable fire-safety requirements, so the exact compliance and listing required should be confirmed with the consultant.

SS 22:1979 is listed as obsolescent on the Singapore Standards eShop and covers sectional tanks constructed from 1220 mm square pressed steel plates. However, it continues to be referenced in Singapore fire-protection specifications. The applicable standard and required LPCB listing should therefore be confirmed with the project consultant.

VERIFY BEFORE AWARD

SS 22 & LPCB requirements

Confirm SS 22 compliance and whether the project requires a current LPCB-listed tank system.

CONFIRM THE COMPLETE SCOPE

Design standard & plate thickness

Check whether the quotation follows BS 1564, SANS 10329 or another specified design and plate-thickness schedule.

DESIGN TO THE STANDARD

Fire protection & non-potable use

HDG pressed steel is intended for fire protection and selected non-potable duties. It is not approved for potable water storage in Singapore.

Want a broader introduction to HDG pressed steel tanks? Learn how the panels are formed, how the hot-dip galvanising process protects the steel, and where these tanks are commonly used.

PDF

PRODUCT INFORMATION

Download Our Water Tank Brochure

View Magtech’s sectional water tank products, applications and available installation services.

Related Works

Highlighted Projects

Project: Marina Bay Sands

Project: Changi Terminal 1

Project: ARC Changi T5

SECTIONAL CONSTRUCTION

How an HDG Pressed Steel Water Tank Is Built

Mild-steel plates are hydraulically pressed into flanged sectional panels to provide structural stiffness. After fabrication, the panels and associated steel components are immersed in molten zinc so the protective coating reaches the surfaces, folds, edges and bolt holes.

The panels are transported separately and assembled on site using sealed bolted joints. Internal, external or hybrid reinforcement is selected according to the approved tank design, structural requirements and required access for inspection and maintenance.

You can compare FRP, pressed steel and stainless steel tanks before selecting a system.

Close-up of bolted HDG pressed steel sectional tank panels showing flanged joints - Magtech
Close-up of bolted HDG pressed steel sectional tank panels showing flanged joints
01

Hydraulically Pressed Panels

Ribbed and flanged steel panels provide the stiffness required to resist water pressure.

02

Hot-Dip Galvanised Finish

Galvanising after fabrication protects panel surfaces, edges, folds and bolt holes.

03

Bolted Sectional Assembly

Modular panels are transported separately and assembled within the available installation area.

04

Reinforcement Options

Internal, external or hybrid reinforcement can be selected according to structural and maintenance requirements.

SIZES & TECHNICAL PERFORMANCE

Confirm the Module, Plate Thickness and Effective Capacity

Tank dimensions and plate thickness depend on the selected module system, design standard and overall tank height. Effective capacity should be confirmed after allowing for freeboard and fittings.

Standard modules

1.0 m / 1.22 m

Metric and imperial square-panel systems

Maximum standard height

4.0 m / 4.88 m

Metric and imperial configuration limits

Typical service life

20–25 years

Subject to site conditions and regular maintenance

Capacity is set by footprint and height. Using 1.22 m imperial modules, a 1220 × 1220 mm tank at one module high holds approximately 1.82 m³, and the tabulated range extends to roughly 1,229 m³ at a 15,860 × 15,860 mm footprint at 4.88 m high. Metric 1.0 m modules run to approximately 507 m³ at 3 m high and 676 m³ at 4 m.

Those are nominal figures with no freeboard. Effective capacity is always lower once freeboard and fittings are accounted for, so confirm the effective requirement rather than the nominal one before a tank is sized. We will do that calculation as part of any quotation.

Plate Thickness Schedule

Panels are supplied in 1.22 m × 1.22 m and 1.00 m × 1.00 m modules as standard. Half modules of 0.5 × 1.0 m, 0.6 × 1.22 m and 0.5 × 0.5 m are available on request, which is what allows a tank to be built to an awkward plant room rather than the plant room being built to the tank.

Plate thickness is set by tank height and by the design standard. SS 22 is our default; SANS is available on request. The difference matters — SS 22 holds most panels at a flat 5 mm, while SANS steps thickness down tier by tier.

Swipe horizontally to view all table columns

Tank HeightPanel TierSS 22 (Default)SANS
1.0–1.22 mBottom and side tiers5 mm3 mm
2.0–2.44 mBottom and side tiers5 mm3 mm
3.0–3.66 mBottom and first tier5 mm4.5 mm
Second and third tiers5 mm3 mm
4.0–4.88 mBottom and first tier6 mm6 mm
Second tier5 mm4.5 mm
Third and fourth tiers5 mm3 mm
Roof covers are hydraulically pressed at 1.5 mm or 3.0 mm, with pitched or domed profiles available on request.

Alternative finishes and linings can be supplied where a specification calls for them. If your project requires something other than standard hot-dip galvanising, contact us with the requirement and we will confirm what can be manufactured.

Panel thickness is the clearest difference between tanks that look identical in a photograph. Some imported panels are supplied at 3 to 4 mm where the equivalent SUNNIK panel is 5 mm. That difference does not show on handover day. It shows in year twelve.

Manufacturing Specifications

Swipe horizontally to view all table columns

ItemSpecification
General Application Water storage for air-conditioner make-up, firefighting, and food production with Food Grade Epoxy Coating.
Standards Rectangular pressed steel sectional water tanks constructed with hydraulically pressed flanged panels conforming to B.S. 1564 and hot-dip galvanised to ISO 1461:2009.
Materials Mild steel used for the plates, stays, cleats and pads conforms to BS EN 10025:2004.
Tank Panels Tank panels measuring 1.22 × 1.22 m or 1.0 × 1.0 m are hot-dip galvanised to ISO 1461:1999.
Tank Covers Standard tank covers are hydraulically pressed, available in 3.0 mm or 1.5 mm thicknesses, and sized at 1.22 × 1.22 m or 1.0 × 1.0 m. The covers are also hot-dip galvanised.
Stays and Cleats The sides and ends of the tank are supported by stays at the junction of two or more plates. The stays and cleats are manufactured from mild steel and hot-dip galvanised.
Bolts and Nuts Bolts, studs, nuts and washers conform to B.S. 4190 and are hot-dip galvanised.
Joining Compounds Non-toxic, odourless PVC foam sealant and butyl sealant, or an approved equivalent, are supplied.
Manhole and Vent Each tank or compartment includes one 600 × 600 mm manhole and one 100 mm diameter vent with an insect-proof attachment on the tank cover.
Ladders Hot-dip galvanised ladders are provided for internal and external tank access. Aluminium ladders are available on request.
Level Indicator A mild-steel or galvanised indirect-reading level indicator is available on request.
B.S. 1564:1975 (Revised) Designed for cold liquid with a density of 1.0 and a temperature not exceeding 38°C.
Tank Height: 4 ft Bottom, sides and ends: 5 mm.
Tank Height: 8 ft Bottom, sides and ends: 5 mm.
Tank Height: 12 ft Bottom, sides and ends: 5 mm.
Tank Height: 16 ft Bottom and first tiers of sides and ends: 6 mm. Second, third and top tiers of sides and ends: 5 mm.
INSTALLATION DETAILS

What Must Be Confirmed Before Installation

The base structure, clearance, reinforcement arrangement, fittings and installation access should be confirmed before manufacturing begins.
01

Support Beam Spacing

Support centres must match the selected system: normally 1.0 m for metric or 1.22 m for imperial modules.

02

Level Base

The supporting base must be level, with a maximum tolerance of ±6 mm across the tank base unless the approved design specifies otherwise.

03

Maintenance Clearance

Allow approximately 500 mm around and below the tank and at least 750 mm above the roof.

04

Concrete Plinth

The reinforced-concrete plinth is normally a separate contractor’s scope and must be completed before installation. Tanks above 3,000 mm may also require steel capping flats on the concrete support.

05

Standard Fittings

Typical fittings include a lockable manhole, insect-proof air vent, ladders, level indicator and flanged nozzles.

06

Approved Installation

Installation must follow the approved tank design and manufacturer’s requirements. Installation by an unapproved party may affect certification and manufacturer warranty coverage.
Water Tank Selection Guide

Which material does my project actually need?

Material is not a free choice in Singapore. The application determines it, and specifying the wrong one produces a rejected submission rather than a saving.

Swipe horizontally to view all table columns

Tank MaterialSuitable ApplicationsStandard or RequirementProduct Page
FRP / GRP Potable & non-potable SS 245:2014 — mandatory for potable water storage since 1 June 2019 View Product →
HDG Pressed Steel Fire protection SS 22; LPCB listing where specified View Product →
SS304 Stainless Steel Non-potable only Suitable for non-potable water; not permitted for potable service View Product →
SS316 Stainless Steel Potable & high-spec PUB’s stipulated standards require Grade 316 stainless steel or better for potable water storage. The complete water service installation must also comply with SS 636 and prevailing PUB requirements View Product →
HDG Pressed Steel WATER TANK BENEFITS

Durable Sectional Storage for Fire Protection Water

HDG pressed steel tanks combine structural strength, corrosion protection and modular construction for demanding fire-water storage applications. We are the sole Singapore distributor for SUNNIK, a manufacturer with more than 40 years in sectional tanks, and we import direct. In a market with no local tank factory, that removes a reseller layer from the price.
01

Fire-Protection Suitability

Widely specified for sprinkler, hosereel and wet-riser water storage in Singapore.

02

Strong Steel Construction

Hydraulically pressed panels provide structural stiffness for large-capacity storage.

03

Galvanised Corrosion Protection

The zinc coating protects panel surfaces, folds, edges and connection points.

04

Suitable for Outdoor Installation

A durable option for exposed plant areas, rooftops and external installations.

05

Flexible Tank Configuration

Metric and imperial modules support different footprints, heights and compartment arrangements.

06

Replaceable Sections

Individual damaged panels can be replaced without necessarily replacing the complete tank.

OUR HDG Pressed Steel TANK SERVICES

Support From New Installation to Replacement and Repair

Installation is carried out by our own Singapore crews rather than subcontracted teams, with several installers bringing 10 to 20 years of experience in sectional tank installation and replacement works.

01

HDG Pressed Steel Tank Installation

Our in-house installation team delivers safe, efficient works with minimal disruption to your operations.

02

HDG Pressed Steel Tank Replacement

We specialise in water tank replacement for ageing or leaking systems, ensuring reliable performance and compliance with current standards.

03

HDG Pressed Steel Tank Repair

We diagnose and repair tank issues quickly, helping to stop leakage, extend lifespan and avoid unnecessary full replacement.

Certifications & Warranty

Supporting Documents for Technical Submission

The applicable document set depends on the approved tank design, fire-protection specification and project consultant’s requirements. Contact Magtech for the current HDG tank certificates, listings and supporting technical documents.
SLS CERTIFICATE 1MX1M PRESSED STEEL TANK TYPE 1 & TYPE 2 (Exp Apr 2028)

SINGAPORE STANDARD

SS 22:1979

LPCB CERTIFICATE (SUNNIK)

Product Approval

LPCB Sunnik

GREENGUARD Gold Certification - HDG (Exp Jun 2027)

LOW EMISSIONS

GREENGUARD Gold

MANUFACTURING DEFECTS

2 Years

Our standard warranty for manufacturing defects is two (2) years from the date of tank completion. This may be reviewed and adjusted upon mutual agreement, depending on project requirements.

WORKMANSHIP

1 Year DLP

The Defects Liability Period (DLP) for workmanship is one (1) year from the date of completion of installation.

COMMON QUESTIONS

If Your Question Is Not Here Contact Us

Short answers to the questions most often raised during tank selection and quotation review.

Pressed steel is mild steel plate that has been hydraulically pressed into a ribbed panel at 45° and 90° to the face. Pressing the panel gives it structural stiffness that a flat plate of the same thickness would not have, which is what allows a bolted sectional tank to hold its shape under load.

They describe different things. Pressed steel is the panel forming process; HDG, or hot-dip galvanising, is the corrosion protection applied afterwards to ISO 1461. An HDG pressed steel tank is both.

For more details, read What is an HDG pressed steel water tank? →

No. HDG pressed steel is intended for fire-protection and selected non-potable duties in Singapore. For potable storage, use an FRP/GRP tank tested for compliance with SS 245:2014 or a stainless steel sectional tank using Grade 316 or better in accordance with PUB’s stipulated standards and prevailing water-service requirements.

Learn more: HDG Pressed Steel vs FRP Water Tanks →

A hot-dip galvanised pressed steel tank has a typical service life of 20 to 25 years in Singapore conditions, provided annual inspection and maintenance are carried out.

Learn more: how long do water tanks last in Singapore? →

Yes. Bolted sectional construction means a damaged panel can be replaced without dismantling the whole tank, which is usually the difference between a repair and a replacement.

Read the Water Tank Replacement Methodology →

It depends on the reinforcement design.

  • Internally reinforced tanks use angle stays inside the tank and are the common standard in Singapore.
  • Externally reinforced tanks carry their bracing outside, leaving nothing structural in the water.
  • Hybrid designs use both and are mainly specified for seismic requirements overseas. Always check which design a quotation is priced on — the difference is significant.
DISCUSS YOUR PROJECT

Enquire About HDG Pressed Steel Tank Installation, Replacement or repair

Send us the required effective capacity, available space, intended water use and project drawings. Our team can review the information and advise on the next step.

Our team will respond within 24–48 hours.

◉ NEED A FASTER RESPONSE? WhatsApp Our Team →

IMPORTANT NOTICE

Office Contact Update

Due to our ongoing office relocation, our main office contact line is currently being redirected while we complete the necessary updates.

For all enquiries in the meantime, please contact us at +65 8700 1377.

We apologise for any inconvenience and appreciate your understanding.